Ultra Lean Indirect Heat Interface Unit

HYDRAULIC CIRCUIT
TI45UL Hydraulic Circuit
1. Brazed plate stainless steel plate heat exchanger (DHW circuit)
2. Manual air vent valve
3. Sensor pocket for heating return sensor
4. Modulating 2-way valve with 12V, 5s stepper motor (normally closed)
5. Spool piece for heat meter ¾”M-110 mm (heat meter available in the following versions: single-jet with M-Bus, radio and ultrasonic)
6. Sensor pocket for heat meter
7. Sensor pocket for heating supply sensor
8. Flow switch (1.5 ÷ 35 l/min)
9. Filter
10. Expansion tank (7 litres)
11. Spool piece for cold water meter ¾”M-110 mm
12. Safety valve heating circuit (3 bar)
13. High efficiency pump type Wilo PARA SC 15/1-7 iPWM
14. Sensor pocket for thermostatic valve primary side (heating side)
15. 230V, 3-point electric servomotor, 120 N, 8 s/mm
16. Brazed stainless steel plate heat exchanger (heating circuit)
17. Filling loop connections
18. Sensor pocket for primary circuit supply sensor
19. Pressure transducer
20. Sensor pocket for DHW sensor
21. Digital controller
CONNECTIONS
IP Primary circuit supply (M-F 1” – ¾” )
MI Heating supply (M – F 1” – ¾”)
RI Heating return (M – F 1” – ¾” )
UP Primary circuit return (M – F 1” – ¾” )
UACS Domestic hot water (M – F 1” – ¾” )
EAFS Domestic cold water supply (M – F 1” – ¾” )
UAFS Domestic cold water return (M – F 1” – ¾” )
TECHNICAL DATA
Maximum temperature: 85°C
Primary circuit max. flow rate: 1500 l/h
Necessary primary circuit head: 12 m H2O / Max. 16 m
H2O pressure transducer: 0.5 ÷ 2.5 bar
Primary circuit maximum pressure: 16 bar
Domestic water circuit maximum pressure: 10 bar
WidthHeating circuit maximum pressure: 3 bar
Hydraulic connections (with interception jig): M-F 1”- ¾”
Width Insulation material: EPP 0.037 W/m*K
Dimensions built-in version (WxHxD): 570x800x160 mm
Dimensions wall-hung version (WxHxD) 560x750x220 mm
Weight (including interception jig): 25 Kg
Type of fluid: H2O
Main component material: UNI EN 12165 CW617N
ELECTRICAL DATA
Module supply: 230V
Power consumption: 70W
Stepper motor – Power supply: 12V
Stepper motor – Running time: 0.5 ÷ 2.5 5 sec.
Rotary electric actuator – Power supply: 230V
Rotary electric actuator – Running time: 24 sec.
Rotary electric actuator – Force: 120N
TI46UL Pressure loss heating circuit

If the hardness of the water exceeds 25 French degrees, it should be treated at the inlet to the system so to prevent fouling caused by hard water or corrosion. Remember, that even small deposits measuring just a few millimetres in thickness will cause problems due to low thermal conductivity and in turn will reduce in performance.

Max working pressure DHW circuit: 10 bar
Min pressure domestic water: 0.2 bar
Heat exchanger material (15/20/30/40 plates): Inox AISI 316
TI45UL Pressure loss DHW circuit

If the hardness of the water exceeds 25 French degrees, it should be treated at the inlet to the system so to prevent fouling caused by hard water or corrosion. Remember, that even small deposits measuring just a few millimetres in thickness will cause problems due to low thermal conductivity and in turn will reduce in performance.

Max working pressure DHW circuit: 10 bar
Min pressure domestic water: 0.2 bar
Heat exchanger material (15/20/30/40 plates): Inox AISI 316